+49 (0)911 62 81 08 - 0        info@a-eberle.de

Languages

Position indicator interface REG-FA

Application:

The REG-FA position indicator interface adapts the tap-changer NO contact bank signal to the REGSys voltage regulator system with AWZ code.

An external auxiliary voltage supplies the NO contact bank; it must be connected to the 'AWZ U+' and 'AWZ GND' connections of the REG-FA. The A1, A2, A3 or A10, A20, A30 signals are transmitted to the REG-FA via switching contacts and translated into BCD code using a code converter. Outputs control the BCD inputs of the REG-D and 6 relay contacts provide the BCD code for further use.

Characteristics:
  • Up to 39 switching positions are converted into BCD Code.
  • The cable length between tap position switch and REG-FA can be up to 100 m.
  • Interference suppression via isolated optocouplers at the inputs
  • Relay contacts  with AC 250 V 2 A, DC 220 V 150 W
  • large auxiliary voltage range of the internal power module

logo a. eberle

Copyright © 2014 A. Eberle GmbH & Co. KG
Design & development: PlanetCreativ

  • A. Eberle GmbH & Co. KG
           Frankenstr. 160, D-90461 Nuremberg
  • +49 (0)911 62 81 08 - 0
  • info@a-eberle.de