+++ ONLY UNTIL DECEMBER 31st: PQ-Box Trade-In Promotion +++ Only a few days left to save on your PQ-Box order +++ Click here for all further information! +++

+++ ONLY UNTIL DECEMBER 31st: PQ-Box Trade-In Promotion +++ Only a few days left to save on your PQ-Box order +++ Click here for all further information! +++

+++ ONLY UNTIL DECEMBER 31st: PQ-Box Trade-In Promotion +++ Only a few days left to save on your PQ-Box order +++ Click here for all further information! +++

All „Supra“ With Your Grid?

Network Feedback in the Frequency Range Between 2kHz and 150kHz

Today’s devices and equipment such as switched-mode power supplies, frequency converters, controlled drives, charging devices for e-mobiles or LED lighting work internally with high clock frequencies in order to regulate power efficiently. These can lead to line-borne as well as field-borne (coupled) interference in the power grid. In this technical report, we explain how you can detect these sources of interference in the grid using suitable measurement technology.

The Change in Energy Technology

The Reason for Energy Efficiency and Cost Savings

In order to use energy more efficiently, we now control many things via power electronics. For example, an asynchronous motor is often replaced by a frequency converter-controlled drive, or a device is equipped with a switched-mode power supply instead of a transformer.

As a rule, the new device technology, unlike the old technology, no longer draws a sinusoidal current from the mains. Power quality measuring devices break down this current into the spectrum of all frequencies. In power quality measurement, we now divide mains perturbations into harmonics, interharmonics and, more recently, superharmonics.

We define harmonics as multiples of the fundamental (example 250Hz = 5th harmonic in a 50Hz fundamental). If frequencies lie between two integer multiples of the fundamental, we call them intermediate or interharmonics. In power quality measurement technology as well as in the standards, all interharmonics of a range are usually combined into one value (example: all frequencies between >350Hz and <400Hz are included in the 7th interharmonic).

High frequencies above 2.5 kHz up to 150 kHz are often called supraharmonics. Oh yes, there are also subharmonics. These are frequencies lower than the fundamental, which can often lead to glitching

The picture shows a frequency spectrum of the voltage from DC to 20 kHz in a public grid. Harmonics as well as supra-harmonics can be seen, which in this case were generated by a frequency converter controlled drive. The highest levels here are at 10kHz with approx. 1.8V.

Typical Cycle Frequencies of Systems and Devices That We Have to Reckon With in Our Networks Today:

  • Frequency inverter drive: 4kHz to 20kHz
  • Solar inverter (400V): 16kHz to 22kHz
  • WK system (MV grid): 2kHz to 6kHz
  • E-Mobile: 10kHz to 80kHz
  • Active mains filters: 8kHz to 20kHz
  • UPS systems: 15kHz to 25kHz
  • EVG luminaires: 20kHz to 200kHz
  • Switched-mode power supplies: 30kHz to 300kHz

Where Do These High Switching Frequencies in Our Electrical Loads Come From?

Example: A bridge rectifier at the input of a CNC machine rectifies the three phase voltages to a DC voltage. This DC voltage is broken down into pulses with different pulse-pause times at a certain cycle frequency to produce a sinusoidal current in the electrical load. This is called “sinusoidal pulse width modulation”. The speed of the motor can be controlled in this way. Loads with very high power, such as a wind turbine, usually have a low switching frequency, while low-power systems operate with much higher cycle frequencies.

The picture shows a diagram of the structure of a frequency converter controlled drive, which consists of a rectifier, a DC link and an inverter.

These cycle frequencies and their sidebands can be detected in the mains current as well as in the mains voltage, which is mapped via the mains impedance.

In the example (Fig. 5) we see the frequency spectrum of the voltage of a load with a cycle frequency of 4.5 kHz at 2.5 V of an industrial plant. A drive operates with this switching frequency. However, this is not the only frequency that is represented in the energy network. There are other frequencies that we receive as a network reaction from this system. With the help of the formula, we get all multiples of the switching frequency and its sidebands calculated.

f_{μ} = n *f_{T} ± 2_{n} * f_{1}

n = 1, 2, 3…
fμ = Cycle frequency of the inverter
f1 = fundamental frequency mains (50Hz)

In our example, this system imprints not only the 4.5kHz but also all multiples of it. Here of 9kHz, 13.5kHz; 18kHz… into the network, as well as additionally their sidebands of +/-100Hz; +/200 etc.

What Are the Problems We Face?

The following problems can now occur in the network due to the supraharmonics:

1. Malfunction of Devices

More and more loads are controlled by very small control signals of higher frequency. Now it can happen that a higher frequency interference signal from a load imprints exactly these frequencies into the network with which another device is controlled. Here is an example: In a hotel that had equipped all rooms with touch dimmer lamps, an industrial company that was producing nearby was able to switch these lamps on and off independently. Since this also happened at night, it was very inconvenient for the overnight guests. In another case, the feedback effects of a solar inverter could cause an automatic milking line for cows on a farm to fail. In both cases, there is no damage, but certain loads in this grid do not function faultlessly.

2. Disruptive Ringing Noises

Another problem that occurs more and more frequently in our networks is disturbing buzzing or ringing noises from loads. Cycle frequencies are often within the hearing range of the human ear. As a rule, humans can perceive sounds up to a maximum of 16 kHz, but people vary greatly in their sensitivity. From an industrial plant, we are already used to the fact that as soon as a CNC machine is working, for example, a ringing noise from the plant can be perceived. However, if the neighbour across the street hears a ringing from a transformer or lighting equipment possibly even at night, then this can be perceived as very disturbing and a remedy for this disturbance must be sought.

3. Equipment Failure or Ageing

The load from cycle frequencies of other loads in the vicinity is also a detriment. Currents of higher frequency are strongly attenuated by inductances such as transformers and thus do not want to flow towards the local network transformer. Rather, these switching frequencies seek out other loads in the vicinity that have a low impedance for these high frequencies. Due to the additional current consumption, these loads are heated up more, since the losses increase as the square of the current P = I²xR. Capacitors can be overloaded or at least age more quickly, since they have a very low impedance for high frequencies.  

XC=\frac{1}{ω*C}
ω=2*π*f

An increased current consumption always means a higher thermal load on the load, which in turn leads to a reduced service life. Why does my LED lamp not last as long as stated on the packaging? Supraharmonics could play a role.

The noise propagation in the network is thus significantly influenced by all devices connected and switched on in the vicinity and less by the line impedances.

A Reaction Was Made in the Voltage Quality Nomenclature.

For a long time, the frequency range from 2.5 kHz to 150 kHz was a standard-free area. The EMC standard IEC61000-2-2 (Environmental conditions – Compatibility levels for low-frequency conducted disturbances in public low-voltage networks) has already reacted and since 2018 has extended the range of limit values from previously 2.5kHz to 30kHz. In 2019, limit values from 30kHz to 150kHz were then introduced and the standard gap was completely closed. Above 150kHz up to at least 30MHz, limit values also apply to the emitted interference of devices and systems. These are checked in a test laboratory in the course of an EMC test for the approval of the device.

This means that today we have a complete range of compatibility levels..

Limits of IEC61000-2-2

Frequency range (kHz) at 50HzCompatibility level in %
2kHz to 3kHz1,4%
3kHz to 9kHz1,4% to 0,65%
Logarithmic decrease with logarithmically increasing frequency
Frequency range (kHz)Compatibility level in dB(yV)
9kHz to 30kHz129,5 to 122 dB(yV)
Linear decreasing with the logarithm of the frequency 9kHz to 30kHz
30kHz to 50kHz122 bis 119 dB(µV)
Limit value linearly decreasing with the logarithm of the frequency 30kHz to 50kHz
50kHz to 150kHz113 bis 89 dB(µV)
Limit value linearly decreasing with the logarithm of the frequency 50kHz to 150kHz
Voltage mVdB (yV)
1000mV120dB
100mV100dB
10mV80dB

Almost every load leaves traces on the net or in other words: “Show me your electricity and I know more about you than you expect”.

I had installed a power analyser (PQ-Box 300) in my sub-distribution in the basement and wanted to analyse the reason for a sporadic tripping of a residual current circuit breaker.

The picture shows the installation location of the measuring device PQ-Box 300 and the current clamps L1, L2, L3, N-conductor. Another large 5th current clamp additionally recorded the differential current of all currents at the connection to the RCD.

In addition to analysing the faulty device in the house that triggers my RCD, I noticed that many loads in my distribution leave their traces in the frequency spectrum. I was able to clearly identify many devices in the frequency range, although they would certainly not have been noticed in the total current of the entire house with all loads. So I could see when the washing machine was running or when my wife was using the hoover, which leaves a clear frequency of 8 kHz in the spectrum.

The picture shows the spectrum of all frequencies of the voltage up to 170 kHz over the period of one week in a kind of 3-D representation. The colour gradients show the level of the respective frequencies.

It was interesting for me that even very small loads like one of the children’s Playsations 4 could clearly be found in the frequency spectrum at 64kHz, although I had measured two floors away. Thus, I was able to monitor the child’s requirement to play only for a maximum of one hour a day, even if I was not at home.

The picture shows the 64kHz frequency on the voltage phase L1 in the distribution. Since the children’s room 1 is also connected to phase L1, these are the times when our teenager gambles. But he doesn’t let us tell him what to do.

The different level heights are due to other loads that are currently switched on and their compensation effect. Since many other devices in the house are switched on at 8:30 p.m., for example, they absorb some of the energy of the 64 kHz frequency and thus reduce the interference level that I can measure in the distribution. At 1 a.m., only a few loads are still active, here the levels have a stronger effect and can be measured with increased values in the distribution in the basement.

The 12-year-old has a time limit of 1 hour and this was clearly exceeded in this case with 2 hours.

The picture shows the 64 kHz frequency on the voltage of phase L3 in the distribution. This phase also supplies the second children’s room and can therefore be clearly assigned to the younger son.

The PQ-Box 300 power quality analyser uses 24-bit analogue-digital input converters and a sampling rate of 409.6 kHz. Due to the extremely high resolution, even the smallest interference levels of a few millivolts can be measured and assigned very precisely. The measurement range for super harmonics covers frequencies up to 170 kHz. These can be permanently recorded without gaps over a long measurement period. For the problems described above, it is rarely possible to detect the cause via a short online measurement. As a rule, all measurement data should be recorded without restriction for at least one week in order to later be able to clearly assign the time of the disturbance and also the cause by correlating the various measurement values.

Conclusion

Network feedback in the frequency range between 2kHz and 150kHz has been steadily increasing in our energy networks for several years and this trend will continue, also strongly driven by the energy transition. On the other hand, we are controlling more and more devices and systems with small signals. Mutual interference cannot be ruled out. Today, the rules of the game for the public grid are laid down in the EMC standard IEC61000-2-2, which regulates with its limit values up to 150 kHz whether a load introduces too high interference levels into the grid at the connection, or whether a disturbed device has too low interference immunity. Measurement technology can prove this. If the interference level is still below the limit values and a load is negatively influenced, the interference immunity is probably designed too low here. If the limit value of the standard is exceeded, it is almost certain that the source of the interference is providing too much feedback into the network.

The PQ-Box 300 power quality network analyser used employs 24-bit analogue-digital input converters and a sampling rate of 409.6 kHz. Due to the extremely high resolution, even the smallest interference levels of a few millivolts can be measured and assigned very precisely. The measurement range for super harmonics covers frequencies up to 170 kHz. These can be permanently recorded without gaps over a long measurement period. For the problems described above, it is rarely possible to detect the cause via a short online measurement. As a rule, all measurement data should be recorded without restriction for at least one week in order to be able to clearly assign the time of the disturbance and also the causer later by correlating the various measurement values.

Autor
Jürgen Blum, Product Manager Power Quality Mobile

Want More Information About Our Products?

Contact Us Here!


Contact Us

News From the Product Group

PQMobil - News

General Knowledge

Harmonics

Harmonics are waves whose frequencies are an integer multiple higher or lower than those of the fundamental oscillations. They arise due to non-linear loads in the grid when the electrical voltage is distorted due to various influencing factors. Learn more about harmonics in this article!

Read more

Training Video

»PQMobil« Training Video 6: Presentation of WinPQ mobile 7.1

In this video we introduce you to all the new features & functions of the latest version of the analysis software »WinPQ mobil 7.1« for our portable power quality analysers. Enjoy the video and the new possibilities with your PQ-Box from A. Eberle.

Read more

Blogpost

International Partner Week 2024 – a Look Back

Our International Partner Week 2024 - many old friends and new faces were our guests, it was a pleasure.

Read more

Training Video

»PQMobil« Training Video 5: Trigger and Fault Record Settings

Discover the best trigger settings for your »PQ-Box« to accurately record network disturbances. The video shows how to configure the half-cycle, oscilloscope, and transient recorders to reliably capture essential measurement data.

Read more

Blogpost

PQ-Box Trade-in Promotion: Only From 1 September to 31 December 2024

For a limited time: Receive a discount for the trade-in of your PQ-Box 100 or a comparable external old device (3-phase power quality analyser). Click here for further information!

Read more

General Knowledge

Voltage Monitoring

Find out everything you need to know about voltage monitoring in this article. What is voltage monitoring, why is voltage monitoring essential for both energy supply companies and industrial companies and how is it implemented in compliance with standards?

Read more

General Knowledge

What Is Load Profile Measurement/Power Measurement?

This article explains the definition and difference between load profile measurement (RLM), power measurement and measuring the standard load profile. These are important methods for accurately recording energy consumption in commercial, large industrial plant as well as in the public energy grid.

Read more

Training Video

»PQMobil« Training Video 4: Create and Configure PQ Reports With Software WinPQ Mobil

This video explains everything about creating and configuring power quality reports with »WinPQ mobil«.

Read more

Webinar

»PQMobil« Webinar: Grid Analysis in Public & Industrial Power Grids With A. Eberle PQ-Boxes

Webinar recording from 2024-02-22: »PQMobil - Grid Analysis in Public & Industrial Power Grids with A. Eberle PQ-Boxes«.

Read more

Training Video

»PQMobil« Training Video 3: Usability & Functions of the PQ-Box App

This video gives you an introduction to the usability and functions of the »PQ-Box App« for our portable power quality analysers.

Read more

Training Video

»PQMobil« Training Video 2: Menu Navigation and Operation of the PQ-Box

In this short introductory video, we present to you how to navigate and operate our portable power quality analysers »PQ-Box 150«, »PQ-Box 200« & »PQ-Box 300« of the PQ-Box family.

Read more

Training Video

»PQMobil« Training Video 1: Getting Started With the PQ-Box

This video shows in detail how to connect the »PQ-Box« and record measurements. The »WinPQ mobil« software is then used to visualize and analyse the measurement data and create a report.

Read more

Special Publication

Ferrari´s Meter vs. Electronic Meter

This technical report analyzes a power measurement at a large industrial customer. The customer records very high currents and fifth harmonic voltages during production time, which leads to poor voltage quality.

Read more

General Knowledge

Residual current

In this article, you will learn about residual current measurement & residual current monitoring and why it is important to measure residual current.

Read more

General Knowledge

Power Quality

Good power quality is characterized by the fact that the mains voltage actually arriving at the consumer matches the mains voltage promised by the utility company.

Read more

General Knowledge

Reactive power – definition, calculation and measurement

The key role of reactive power in electrical engineering: definition, calculation, measurement and the differences to active power and apparent power. Find out how reactive power influences the efficiency of electricity grids and shapes energy transmission.

Read more

General Knowledge

What is apparent power and how is it calculated?

This article addresses the question of what apparent power is and how to calculate it. An understanding of apparent power is crucial for the correct dimensioning of inverters and therefore for the optimum efficiency and performance of photovoltaic systems.

Read more

Special Publication

Angle Determination of Voltage and Current Harmonics in Practice

Today's devices and equipment such as switched-mode power supplies, frequency converters, regulated drives, charging devices for e-mobiles or LED lighting work internally with high clock frequencies in order to regulate power efficiently. These can lead to both conducted and field-bound (coupled) influences in the energy grid. In this technical report, we explain how you can detect these sources of interference in the grid using suitable measuring technology.

Read more

General Knowledge

Power Quality Analysis: Tips and Tricks II

Useful tips & tricks for handling Power Quality measuring devices and typical user errors - now in our two-part article! This article provides further insights and practical tips and application examples for power quality analysis.

Read more

General Knowledge

Power Quality Analysis: Tips and Tricks I

Useful tips & tricks for handling Power Quality measuring devices and typical user errors - now in our two-part article! This article explains tips and tricks for performing power quality measurements. It explains which connection errors can be made and which preliminary considerations should be made before using a measuring device.

Read more

General Knowledge

Four Ways to Measure Current

The following technical report examines various methods for measuring current. It discusses how currents are measured using power analyzers and current clamps. The respective advantages and disadvantages of different technologies such as shunts, normal current clamps, hall effect sensors, etc. ar also evaluated.

Read more

General Knowledge

Cos ϕ vs. Power Factor λ – Practice

This second technical report on the subject of reactive power and in particular the distortion reactive power supplements the first contribution "Cos ϕ vs. power factor λ – Theory". In this article, the voltage and current of an incandescent lamp are measured in an online measurement using a power analyzer.

Read more

General Knowledge

Cos ϕ vs. Power Factor λ – Theory

This technical report discusses the distinction between power factor and cosine phi. Cosine Phi, formerly widely known as the ratio of active power to apparent power, however, has a different meaning for many consumers today.

Read more

Special Publication

Mains Feedback Interferes With Protective Devices

In a photography and design studio, located in a large industrial park, a RCD tripped frequently. Due to the permanent power cuts, the employees of the studio could not work properly. This article shows how we found a solution for this problem using our Power Quality devices.

Read more

Special Publication

Creating Power Quality Surveys With PQ-Box and WinPQ Mobil Software

The following report displays the PQ-Box and WinPQ mobil software interact to allow an evaluation of the disturbance levels at a measuring point according to approved grid norms.

Read more

Contact request:



* Mandatory

Your data is being processed

a-eberle kontakt newsletter ×

Our seminars &
webinars

► Register here!

x