Current Measurement

Four Ways

The following technical report examines various methods for measuring current. It discusses how currents are measured using power analyzers and current clamps. The respective advantages and disadvantages of different technologies such as shunts, normal current clamps, Hall effect sensors and Rogowski coils are considered. The possible measurement errors are also addressed.

1. Current Shunt

1 Example illustration: current shunt

The use of a shunt is particularly suitable when high precision is required in the measurement, as is the case, for example, in engine test benches. A very accurate resistor, for example with a resistance value of 0.1 Ohm, is used. The current flow of 100 amperes through the shunt results in a voltage drop of 10 volts, which is linearly proportional to the current flowing through it. The measurement principle is very accurate and allows recording of high frequencies as well as AC and DC signals. The disadvantage is that the shunt must be installed in the mains, which is usually too costly for short-term measurements with a mobile power analyzer. It should be noted that the current shunt can be installed in the phase with high potential to ground, as well as in the N conductor. It is important to consider the potential at which shunts are located when using them. For example, a power analyzer might measure the voltage output of 10 volts but a potential of the shunt to ground could overload the meter. Therefore, it is important to carefully consider whether the use of a shunt is favorable in a particular application and whether the meter is also rated for the high potential.

2. Current Clamps With Metal Core

2 Current clamp with metal core from A. Eberle
3 Physical principle of operation Current clamp with metal core

The conventional technique for measuring current is to use fixed current clamps. These work on the principle of a transformer. The scheme of such a clamp is shown in the figure. The current cable is considered as winding 1. Via an alternating magnetic field in the iron core, a current is induced in the second winding, which is indirectly proportional to the current in the conductor.
For example, if a current of 1000 amperes flows in the conductor and the transformer has 1000 windings, the current at the output of the current clamp will be 1 ampere. The ratio between the two currents is therefore 1:1000.

Modern current clamps often have a terminating resistor which does not supply a current at the output, but a voltage in millivolts proportional to the current. However, the measuring principle remains the same. This makes it possible to leave the current transformer connected to the mains without danger and to disconnect it from the measuring device. This current transformer does not necessarily have to be short-circuited, unlike current-to-current transformers which must not be
operated in the open state. Special care must be taken when using current clamps with metal cores, as even a small air gap can lead to large measurement errors. To avoid this, an interlock has been built into the mini current clamps of the PQ-Box. However, at higher currents, such as in the 1000-3000 amp range, the clamps become very heavy, large and unwieldy, making
maneuvering around large conductors difficult. In this case, the use of Rogowski current clamps is a more practical alternative.

3. Hall Sensor Current Clamps

If both AC and DC signals are to be measured, the effort required for the measurement technology is somewhat greater. A passive clamp cannot be used in this case. Instead, the Hall effect can be used in metrology. This involves a semiconductor component to which a current
flow is connected. When this semiconductor element is in a magnetic field, charge carrier separation occurs in the Hall conductor component. This implies that the charge carriers are shifted to one side in the magnetic field. This voltage of the Hall sensor element is proportional to
the magnetic field. With this effect, both AC and DC currents can be measured.

4 Hall sensor current clamps from A. Eberle for AC and DC currents
5 Principle for the construction of a Hall effect clamp

The use of AC and DC current clamps has both advantages and disadvantages. Although these clamps are used very frequently, they are not used as standard in all measuring devices. One disadvantage of these clamps is that they are sometimes very sensitive to temperature.
Usually, one has to calibrate a DC current clamp to the value 0 via a key or a rotary knob before each measurement. However, this can lead to relatively large errors in the measurement technique for long measurement periods, such as monitoring a solar system over 7 days, due to temperature fluctuations between day and night.
Another limitation is the need for a power supply. Most current clamps are designed to run on batteries, which is inconvenient for longer measurement periods. However, there are clamps that can be powered by an external power supply, allowing for longer measurement periods. When using current clamps, it should always be noted that there are various sources of measurement error, such as temperature drift.

4. Rogovski Coils

6 Rogovski coils by A. Eberle

Rogowski clamps are very user-friendly, as they are available in all lengths and sizes, and are very flexible in design. One customer request is for the clamp to be as thin and small as possible, so that these loops can be accommodated even in very confined spaces. However, the advantage of a very thin current loop also comes with a disadvantage in terms of measurement technology.
The output signal depends on the diameter of the head. A larger diameter leads to a larger output signal. Therefore, although a thin clamp can be used in tighter spaces, the output signal is lower and thus smaller currents can only be detected with a larger measurement error. This is a
limitation of physics that cannot be circumvented.

A Rogowski coil consists of a rubber core that behaves magnetically like air and is therefore also called an air coil.

7 Operating principle Rogowski coil (also known as "air core coil")

To reduce measurement errors when measuring small currents, it is possible to wind the coil twice around a conductor. Since the measured value would now be doubled, this can be corrected very easily by adjusting the transformer ratio in the settings of the PQ box to the factor x0.5.
It should be noted that Rogowski current transformers can only measure AC currents and not DC.
Each Rogowski coil needs an integrator at the output to trace the output signal back to the original current signal. Most Rogowski coils have electronics built into the cable, which usually also requires a power supply. All PQ boxes from A-eberle have two separate current inputs. One input for current clamps and one input for Rogowski coils. Due to a coding in the plug of the current clamp, the measuring device automatically recognizes the correct clamp type. A power supply for these current clamps is therewith not necessary, additionally the precision is improved, as the measuring signal is not converted twice.

With regard to measurement errors, the information on the current clamp supplier's data sheet should be taken into account

8 Technical data of a Rogowski coil

Calibration and manufacture of the clamps provide relatively small measurement errors of 0.5 percent of the measured value when using Rogowski current clamps. The greatest error factor is often the position sensitivity of the clamp. Optimum accuracy is achieved when the conductor is positioned exactly centered in the middle of the clamp. In practice, however, the positioning of the conductor influences the measurement result by up to 2%. Other factors that influence accuracy are linearity, temperature influences and neighboring fields. Thus, currents in
neighboring conductors also influence the measurement result. This error is up to 1 % of the neighboring currents. It becomes problematic when measuring small currents in the vicinity of conductors with large currents. There, the error can also be up to 100 percent of the measured
value. It is therefore necessary to carefully consider the ambient conditions, especially when measuring low currents.
The use of mini current clamps is usually more suitable for the measurement of very small currents.

Angular Errors

Measurement errors, especially angular errors, can be caused by the sampling of voltages and currents. As a rule, voltages are tapped off in a fixed manner, while currents are measured with the aid of current clamps. However, each current clamp has a slight phase error, which can cause the measured current to be displayed leading or lagging. The meter calculates all the powers from the samples of the voltages and the currents.
As an example, it will be shown how angular errors are noticeable in the power measurement quantities.

9 Calculation example angular error 1

An example 1 is a network where the cosphi is quite good, with a phase angle of 10 degrees between fundamental voltage and fundamental current. A phase error of a current clamp of one degree can give the following measurement results in the meter display for an actual value of 0.984 for the cosphi: Max: 0.981 or Min: 0.967.
This corresponds to an error of 0.3 % for the cosphi as well as for the active power.

In example 2, a measurement at an extremely large phase angle is used. This application is to determine the active power losses at a line reactor of 2.3 MVA reactive power in a medium voltage network. The cosine Phi of this inductor should be 90 degrees if possible. In our case, the
phase error is 89 degrees.
An additional angular error of one degree of the current clamp or even of a secondary measuring transformer can now lead to a measuring error of up to 200 percent.
In this case, the active power losses of this coil can now be between 0 and 200% of the true measured value. However, for the reactive power in this case the measurement is very precise.

10 Calculation example angular error 2
11 Input angle correction factor Software PQ mobile by A. Eberle

For evaluations in the network where correct angle measurements are very important, such as when measuring in a medium voltage network or via current transformers in a low voltage network, the correction of the angle errors of the various transformers can become very important.

In all PQ boxes, an angle correction factor can be stored for the calculations of the power measurement quantities and phase angles. This allows angular errors to be corrected very easily for measurements where the angular error is crucial.

Author
Jürgen Blum, Product Manager Power Quality Mobil

Want More Information About Our Products?

Contact Us Here!


Contact

News From the Product Groups

Power Quality | – News

Blogpost

International Partner Week 2026 - Exchange, knowledge transfer and collaboration in Nuremberg

We were delighted to welcome our international partners to Partner Week 2026. The chance to chat in person, seeing familiar faces and making new acquaintances made the week a special one for us.

Read more

General Knowledge

Electrical Resistance

Electrical resistance is one of the fundamental quantities in electrical engineering. This article explains the definition, unit, symbol, Ohm's law, resistance measurement and the role of resistance in circuits and power networks.

Read more

General Knowledge

Measuring Equipotential Bonding

Measuring equipotential bonding is essential for verifying low-resistance, continuous connections between conductive parts. This article explains equipotential bonding, relevant standards, typical measurement methods and its importance for safety, EMC, power quality and reliable grid operation.

Read more

Blogpost

Power Quality Analysis 2026: Guide to Measurement & Assessment

Power quality analysis 2026: guide to standards, Class A measurement, monitoring, and practical assessment workflows.

Read more

General Knowledge

Insulation Resistance and Insulation Measurement

Insulation measurement helps assess the safety and condition of electrical installations. This article explains insulation resistance measurement, relevant limits, test voltages and practical interpretation in real grid operation.

Read more

Webinar

»PQMobil« Webinar: Power Quality Analysis in Public & Industrial Power Grids with A. Eberle PQ-Boxes - Part 4

Webinar recording from 2026-04-15: »PQMobil - Power Quality Analysis in Public & Industrial Power Grids – Part 4«.

Read more

Blogpost

A. Eberle and Bregal Unternehmerkapital enter into a growth partnership

A. Eberle and Bregal enter into a growth partnership. The partnership with BU is intended to accelerate A. Eberle’s international expansion, innovation and technological advancement.

Read more

Webinar

»PQ-Box ONE« Webinar: The New Single-Phase Power Quality Analyser for Measurements

Webinar recording from 2026-02-25: »PQ-Box ONE« - The New Single-Phase Power Quality Analyser for Measurements

Read more

General Knowledge

Measuring Harmonics: Detecting Disturbances in Buildings

Harmonic distortion and supraharmonics can cause flicker, nuisance tripping and device malfunctions in modern buildings. This article explains how to measure harmonics at the socket outlet and interpret spectra (e.g., around 17 kHz) to identify the root cause.

Read more

Blogpost

Power Quality Monitoring for Electrical Contractors - Mobile Network Quality Measurement with the PQ-Box ONE

How a portable power quality analyzer like the PQ-Box ONE helps electrical professionals identify voltage disturbances, improve documentation and make reliable technical decisions.

Read more

Blogpost

Power Quality Analyzer Guide: Your Entry Point for 2026

Comprehensive 2026 guide to power quality analysers: selection criteria, applications, standards, and future trends for reliable power quality monitoring.

Read more

Blogpost

Short video presentation »PQ-Box ONE«

Ahead of the official launch on February 25, 2026, we are releasing a short video about the new »PQ-Box ONE« that provides an initial overview of the key features of the new PQ measuring device.

Read more

Blogpost

»PQ-Box 150« and »PQ-Box ONE«

PQ-Box 150 and PQ-Box ONE in practical comparison: PQ-Box 150 and PQ-Box ONE both deliver Class A measurements, but differ in terms of installation, handling and areas of application.

Read more

Blogpost

Power Quality Monitoring: Risks of Poor Power Quality

Power quality monitoring translates “invisible” disturbances into measurable causes and KPI impacts. This guide explains common power-quality events and a practical workflow to measure, evaluate and derive corrective actions.

Read more

Webinar

»Cyber Security« Webinar: A Challenge for European Energy Companies

Webinar recording from 2025-11-26: »Cyber Security« - A Challenge for European Energy Companies

Read more

Blogpost

A. Eberle at the Schwabach City Run 2025

A. Eberle was represented by 37 participants at the 2025 Schwabach City Run, setting a new internal record for participation. Particularly noteworthy is Benjamin Rentsch's first place in the M 35 40 age group and third place overall.

Read more

Training Video

»PQMobil« Training Video 8: Setting up remote access for the PQ-Box

This video shows how to configure a PQ-Box remotely via Wi-Fi, LAN, network, and the Internet using a VPN tunnel, view live data, and transfer measurement data. Enjoy the video.

Read more

General Knowledge

Total Harmonic Distortion (THD) in Low Voltage Networks

This study examines harmonic distortion in modern low-voltage grids, showing real measurement data, key standards (EN 50160, IEC 61000-3-2/-4-30) and practical ways to reduce THD in applications such as EV charging, PV systems, battery storage and hybrid working environments.

Read more

Special Publication

Power Quality Monitoring in Buildings - A Key Factor in Modern Building Design

Discover how Power Quality Monitoring in Buildings improves reliability, efficiency and grid stability. Learn more in our technical article.

Read more

Special Publication

Continuous Power Quality Monitoring in the Jupiter Data Centre - Voltage Quality at Exascale Level

With JUPITER, Forschungszentrum Jülich operates Europe's fastest supercomputer and sets new standards for energy efficiency, grid stability, and standard-compliant power quality with PQSys from A. Eberle.

Read more

General Knowledge

Voltage Measurement Can Improve the Quality of Supply

A short study by EWI and Fraunhofer IEG shows that mandatory voltage measurements and stricter regulation of voltage quality are necessary to ensure grid stability in Germany in light of the energy transition.

Read more

General Knowledge

Power in Multiphase Systems

This technical report highlights the special features of power transmission in three-phase systems and offers valuable insights into the optimisation and analysis of modern power grids.

Read more

Webinar

»PQMobil« Webinar: New Features/Functions for Your PQ-Box/es: Presentation of WinPQ mobil V8 & V7 legacy

Webinar recording from 2025-07-29: »PQMobil - New Features/Functions for Your PQ-Box/es: Presentation of WinPQ mobil V8 & V7 legacy«.

Read more

Blogpost

Visit From the Rudolf Diesel Technical School at A. Eberle

We were happy to welcome you, Rudolf-Diesel-Fachschule! Yesterday, we had the pleasure of welcoming two classes of future electrical engineering technicians from the Rudolf-Diesel-Fachschule Nürnberg to our company in Nuremberg.

Read more

Blogpost

TOP 100 Awards 2025: Innovation for the Energy Future

💡 As part of the TOP 100 Awards 2025, we were honored to receive a special recognition last week in Mainz – personally presented by TV host and science journalist Ranga Yogeshwar.

Read more

Contact request:



* Mandatory

Your data is being processed

a-eberle kontakt newsletter ×

The download started automatically in a new window.

How did you hear about us?
Consent to data transfer*

* Mandatory fields