Parallel Operation of Transformers With Tap-Changers

Securely controlled with the »REGSys®« voltage regulation system

Introduction

Parallel operation of transformers enables flexible power distribution and provides reserve capacity during outages. Transformers with tap-changers require coordinated voltage control so that different open-circuit voltages do not cause unwanted circulating reactive currents. Digital regulators such as the freely programmable REGSys® voltage regulation system perform this task with high control quality.

In brief: During parallel operation, the regulators must consider both the busbar voltage and the loading of the participating transformers. REGSys® provides master-slave, master-follower, ΔIsinϕ, ΔIsinϕ(S) and Δcosϕ control methods for this purpose.

The core of the REGSys® voltage regulation system (Figure 1) is the REG-D® voltage regulator. In addition to voltage control, it performs measurement, recording and statistical functions. Users configure the regulator either from its keypad or through the menu-guided WinREG software on a PC. Communication interfaces are particularly important for parallel operation. The dual E-LAN regulator bus (RS485 interface) enables data exchange between up to 255 regulators. This removes the need for costly additional measuring equipment or separate parallel control units.

REGSys® voltage regulation system with REG-D®, PAN-D and REG-PED in a 19-inch subrack
Figure 1: The REGSys® voltage regulation system consists of the REG-D® voltage regulator, the PAN-D monitoring unit and the REG-PED SCADA communication card in a 19-inch subrack.

The COM 1, COM 2 (RS232) and COM 3 (RS485) serial interfaces connect PCs, modems, supplementary interface modules and higher-level SCADA systems. Analogue and binary inputs and outputs support a wide range of measurement and control functions around the transformer. They can provide tap position feedback or implement a setpoint changeover, for example. Figure 2 shows how the system can be expanded to include Petersen coil control and earth-fault location.

Overview of REGSys® for voltage regulation, communication and additional applications
Figure 2: Overview of REGSys®

Key Points for Parallel Operation of Transformers

  • Different open-circuit voltages can cause substantial circulating reactive currents because transformer impedances are low.
  • Master-slave and master-follower control use matching tap positions and are particularly suitable for identical transformers.
  • ΔIsinϕ and ΔIsinϕ(S) determine the circulating reactive current from measured reactive currents; ΔIsinϕ(S) also considers rated power.
  • Δcosϕ operates without an E-LAN connection and serves as an emergency programme in the REG-D® if bus communication fails.

Parallel Operation of Transformers With Tap-Changers and REGSys®

Controlling a single transformer is straightforward, but the conditions become more complex during parallel operation. Several transformers can share the required power and provide reserve capacity during outages. Where several feeders require supply, operators can connect the transformers in parallel to different busbars according to demand. This allows the system to cover power peaks flexibly.

Figure 3 shows the parallel connection of n transformers as an equivalent circuit and explains why parallel operation requires special precautions. If the driving voltage u1 is higher than u2 to ux, the circulating currents icir2 to icirx flow. Their magnitude depends on the short-circuit impedances Zsc1 to Zscx and on the differences between the open-circuit voltages u1 – u2 to u1 – ux. Transformer impedances are normally very low. Transformers with mismatched tap settings can therefore carry substantial circulating currents, which may overload them or at least produce an unfavourable load distribution. The following equations show these relationships:

iT1 = i1 + icir2 + … + icirx (1)
iT2 = i2 – icir2 (2)
iTx = ix – icirx (3)
Equivalent circuit of transformers connected in parallel with circulating currents
Figure 3: Parallel connection of n transformers – equivalent circuit

Why Do Circulating Reactive Currents Complicate Control?

The example shows that all circulating currents place an additional load on transformer T1, while each circulating current relieves the corresponding other transformer. Transformer impedances are strongly inductive and their active component is negligible. These currents are therefore also called circulating reactive currents.

Voltage control also loses sensitivity because a change in the individual open-circuit voltages u1 to ux affects the total busbar voltage only partly. If the impedances Zsc1 to Zscx are equal and the control changes one transformer by Δux, the following applies:

u’tot = utot + Δux / n (4)

Equation (4) shows that with three transformers connected in parallel (n = 3) and equal impedances, a voltage change at one transformer affects the busbar voltage by only one third. This makes voltage control considerably more difficult. If transformers at higher tap positions compensate for transformers at lower tap positions, the busbar voltage may be correct while circulating currents still flow. Parallel control therefore requires additional measured variables.

Control Methods for Parallel Operation

REG-D® Control Methods and Their Applications

REG-D® uses two fundamentally different groups of voltage control methods. Master-slave and master-follower control the voltage and tap positions. ΔIsinϕ, ΔIsinϕ(S) and Δcosϕ also consider the circulating reactive current. Table 1 and Figure 8 compare the applications and requirements of these methods.

MethodPrinciple and application
Master-slaveOne master issues tap commands and the slaves follow. The method is particularly suitable for identical transformers.
Master-followerThe follower reads the master tap position via E-LAN and independently corrects an initial tap difference.
ΔIsinϕThe method determines circulating reactive current from the measured reactive currents and distributes the target reactive current equally.
ΔIsinϕ(S)The calculation also considers rated power, allowing the reactive current to be distributed in proportion to transformer ratings.
ΔcosϕThe method requires no bus connection and suits widely meshed networks as well as emergency operation after an E-LAN failure.
Table 1: Overview of the control methods described for parallel operation
REG-D® control methods for parallel operation of transformers
Figure 8: REG-D® control methods for parallel operation and their applications

Master-Slave and Master-Follower Methods

These methods bring the transformers to matching tap positions. With master-slave control, one regulator leads while the other regulators follow its tap commands. With master-follower control, the follower reads the master tap position via E-LAN and independently moves to the same position. A deliberate tap difference present at the start remains unchanged with master-slave control. The master-follower method corrects this difference.

Both methods are particularly suitable for identical transformers. They can also operate transformers with different rated powers. In that case, equal tap positions must produce equal transformation ratios and therefore equal open-circuit voltages. For good control results, the relative short-circuit voltages of the transformers must not differ by more than 10%.

Circulating Reactive Current Methods

These methods determine the circulating reactive current from the currents at the transformer infeeds. They then minimise it by changing the transformer tap positions selectively.

ΔIsinϕ Method

A simple measurement of the transformer reactive current is not sufficient to determine the circulating reactive current. An inductive load can also cause reactive current (see ix in Figure 3). With two transformers in parallel, the circulating reactive current equals half the difference between the two measured reactive currents. The calculation eliminates the load-related component. With several transformers, the method adds all reactive currents and divides the total by the number of transformers. The result is the reactive current that each transformer would need to supply to cover the load's reactive power demand. According to Figure 3:

iL,tot = iT1 + iT2 + … + iTx (5)

Substituting equations (1) to (3) into equation (5) gives:

iL,tot = i1 + icir2 + … + icirx + i2 - icir2 + ix - icirx (6)

All circulating currents cancel out in equation (6). This gives:

iL,tot = i1 + i2 + … + ix (7)

The relationships in equations (5), (6) and (7) also apply to the reactive components IQx. Adding the transformer reactive currents gives the total load reactive current (see Figure 4).

Vector diagrams for three transformers in parallel showing reactive current components
Figure 4: Vector diagrams for n = 3

Calculating the Target Reactive Current

To determine the target reactive current per transformer, the method divides the total reactive current by the number n of transformers. Each transformer would need to supply this target value to cover the reactive power demand of the loads. The circulating reactive current icirQx of a transformer is therefore the difference between the measured reactive current and the target reactive current:

icirQx = iQx - (iQ,tot · 1/n) (8)

icirQx: circulating reactive current of transformer No. x
iQx: reactive current component of transformer No. x
iQ,tot: reactive component of the total current across all transformers

ΔIsinϕ(S) Method

The ΔIsinϕ(S) method extends the ΔIsinϕ method by considering the rated powers of the transformers. This additional information allows the reactive current to be distributed according to the respective transformer ratings (see Figure 5):

icirQx = iQx - (iQ,tot · Sx/Stot) (9)

where:
Sx: rated power of transformer No. x
Stot: total rated power of all transformers
Reactive current loading of transformers in parallel with different rated powers
Figure 5: Reactive current loading of transformers connected in parallel with different rated powers

Δcosϕ Method

The Δcosϕ method has a special role among the parallel control methods. If several transformers feed a widely meshed network, the regulators may be unable to communicate via E-LAN. They can then neither exchange reactive current values nor calculate the circulating reactive current from these values. The operator first specifies the network power factor cosϕ as the setpoint. From the busbar voltage and transformer current, the regulator calculates the reactive current that would occur if the transformer cosϕ matched the network cosϕ. If the actual reactive current is higher, the regulator moves the transformer to a lower tap. If it is lower, the regulator moves it to a higher tap. The circulating reactive current is calculated as follows (see Figure 6):

icirQx = iTxsinϕact - iTxsinϕset (10)
Vector diagram for the Δcosϕ control method
Figure 6: Vector diagram for the Δcosϕ method

Integration Into Voltage Control

Voltage control alone is not sufficient for transformers in parallel. The circulating reactive current control therefore overlays the voltage control and counteracts unwanted circulating reactive currents (Figure 7). The control variables YU and YP are:

YU = (Uact – Uset) / ΔUperm (11)
YP = IcirQx / IcirQperm (12)

where:
Uact: actual RMS voltage
Uset: RMS voltage setpoint
ΔUperm: permissible control deviation
IcirQperm: permissible circulating reactive current
Interaction between voltage control and circulating reactive current control during parallel operation
Figure 7: Influence of circulating reactive current control on voltage control

Deriving Tap Commands From the Control Variables

The resulting control variable Y is:

Y = YU + YP (13)

Equation (13) determines the tap commands. At Y > +1.0, the regulator issues LOWER; at Y < -1.0, it issues RAISE. The regulator controls voltage and circulating reactive current independently within their permissible deviations. If minimising the circulating reactive current would change the voltage beyond its permissible range, all transformers in parallel correct this deviation together. This prevents a permanent voltage control deviation.

Limiting the Influence of the Δcosϕ Method

The Δcosϕ method also has a special effect on voltage control. If the network cosϕ differs from the configured setpoint, it influences the voltage control. The remaining control deviation ΔU depends on the phase angles ϕset and ϕnet, the apparent current I, the permissible control deviation ΔUperm and the permissible circulating reactive current IcirQperm:

ΔU = ΔUperm · (sinϕset – sinϕnet) · I / IcirQperm (14)

Equation (16) shows how to limit this influence. In Figure 7, the parameter b defines the maximum permitted magnitude of YP.

|YP| < b (15)

This limits the remaining control deviation ΔU to:

ΔU = b · ΔUperm (16)

With strongly fluctuating loads and corresponding changes in the network cosϕ, a self-learning method can adjust the cosϕ setpoint. This avoids permanent voltage deviations and impermissibly high circulating reactive currents.

Safety Measures During Communication Failures

With all methods except Δcosϕ, the regulators involved in the parallel connection exchange the required data via E-LAN. Reliable control must continue if the E-LAN connection fails. Because Δcosϕ operates without a bus connection, it serves as an emergency programme. REG-D® includes this emergency programme as standard.

During normal operation with ΔIsinϕ or ΔIsinϕ(S), the regulator continuously measures the network cosϕ. After a bus failure, it uses the last measured value as the cosϕ setpoint and starts the Δcosϕ method. Once communication is restored, REG-D® returns to the previously active parallel control method.

If the bus connection fails during master-slave or master-follower operation, the slave automatically returns to individual regulator operation and issues an error message.

Simulating Parallel Operation With REGSim

Figure 8 provides an initial theoretical indication of which parallel control method suits a particular system. REGSim (Figure 9) can simulate these methods in any operating configuration of transformers, network and loads. It uses the same control algorithms that are implemented in the regulator. Users can configure parameters such as rated voltage and transformer impedance.

REGSim therefore represents the REGSys® voltage regulation system in a specific system situation. Without intervening in the real system, users can examine how the control responds to extreme conditions such as load steps or earth faults. They can also estimate voltage stability and the number of tap operations in advance. The software is also suitable for training.

REGSim user interface with three transformers connected in parallel
Figure 9: REGSim user interface with three transformers connected in parallel

Automatic Parallel Operation

The ParaGramer (Figure 10) supports the automatic preparation of parallel connections and visualises switching states online. It shows the participating transformers, including circuit-breakers, disconnectors, bus couplers and bus sectionalising points, in a single-line diagram. Each regulator receives a complete busbar image through binary inputs. From the switching states, the system automatically recognises which transformers feed the same busbar in parallel. It treats busbars connected through bus couplers as one busbar.

In Figure 10, transformers T1 and T3 operate on busbar a, while transformer T2 feeds busbar b. ParaGramer can also represent high-voltage busbar configurations. It therefore supports the reliable implementation of a wide range of parallel connections with little effort.

ParaGramer display of transformers and busbars during automatic parallel operation
Figure 10: ParaGramer

FAQ - Frequently Asked Questions About Transformer Parallel Operation

Why does parallel operation of transformers require special control?

What is circulating reactive current in transformers?

When are master-slave and master-follower methods suitable?

What is the difference between ΔIsinϕ and ΔIsinϕ(S)?

When is the Δcosϕ method suitable?

What happens if the E-LAN connection fails?

How does REGSim support the selection of a parallel control method?

Automatic Voltage Regulation With REGSys® - Proven, Multifunctional and Flexible

Do You Have Questions About Our Products?

Contact Us Here!


Get in Touch

News From the Product Groups

REGSys® | – News

Blogpost

GRUNDIG AKADEMIE visits A. Eberle

In 2026, the GRUNDIG AKADEMIE Nuremberg visited A. Eberle with a group of trainee technicians. During the visit, the participants gained an insight into our company, technical fields of work and potential career paths.

Read more

Blogpost

A. Eberle named one of the TOP 100 Innovators for 2026

As part of the 2026 TOP 100 Awards, we had the honour of receiving a special accolade in Heidelberg last week – presented in person by Christian Wulff, former Federal President and mentor of the TOP 100 competition.

Read more

Webinar

»REGSys®« Webinar: New Requirements and Application Cases for Voltage Regulators in MV/HV-Grids

Webinar recording from 2026-06-10: »REGSys®« New Requirements and Application Cases for Voltage Regulators in MV/HV-Grids

Read more

Blogpost

International Partner Week 2026 - Exchange, knowledge transfer and collaboration in Nuremberg

We were delighted to welcome our international partners to Partner Week 2026. The chance to chat in person, seeing familiar faces and making new acquaintances made the week a special one for us.

Read more

General Knowledge

Transformer Monitoring

Transformer monitoring helps detect critical operating conditions early, reduce outages and improve the safe operation of transformers in power grids and industrial systems.

Read more

Blogpost

A. Eberle and Bregal Unternehmerkapital enter into a growth partnership

A. Eberle and Bregal enter into a growth partnership. The partnership with BU is intended to accelerate A. Eberle’s international expansion, innovation and technological advancement.

Read more

Webinar

»Cyber Security« Webinar: A Challenge for European Energy Companies

Webinar recording from 2025-11-26: »Cyber Security« - A Challenge for European Energy Companies

Read more

Blogpost

A. Eberle at the Schwabach City Run 2025

A. Eberle was represented by 37 participants at the 2025 Schwabach City Run, setting a new internal record for participation. Particularly noteworthy is Benjamin Rentsch's first place in the M 35 40 age group and third place overall.

Read more

Blogpost

A. Eberle welcomes Amarillo as a new REGSys® partner in Mexico

A. Eberle is expanding its international partner network and is pleased to welcome »Amarillo Naranja S.A. de C.V.« as a new »REGSys®«-partner in Mexico.

Read more

General Knowledge

Power in Multiphase Systems

This technical report highlights the special features of power transmission in three-phase systems and offers valuable insights into the optimisation and analysis of modern power grids.

Read more

Blogpost

Visit From the Rudolf Diesel Technical School at A. Eberle

We were happy to welcome you, Rudolf-Diesel-Fachschule! Yesterday, we had the pleasure of welcoming two classes of future electrical engineering technicians from the Rudolf-Diesel-Fachschule Nürnberg to our company in Nuremberg.

Read more

Blogpost

TOP 100 Awards 2025: Innovation for the Energy Future

💡 As part of the TOP 100 Awards 2025, we were honored to receive a special recognition last week in Mainz – personally presented by TV host and science journalist Ranga Yogeshwar.

Read more

Blogpost

University Excursion: Pentecost Excursion of the Friedrich-Alexander-University Erlangen-Nuremberg (FAU)

As a company dedicated to innovation, education, and the energy transition, we are pleased to have once again supported the Whitsun excursion of Friedrich-Alexander University Erlangen-Nuremberg (FAU) this year.

Read more

Blogpost

Further Growth at A. Eberle

Welcome to the team! We welcome our new colleagues at A. Eberle.

Read more

General Knowledge

Voltage Stabilisation

In this article, you will learn why voltage stabilisation in high, medium and low-voltage grids plays a central role in safe and efficient grid operation. You will learn the basics of ‘voltage stabilisation’ and get to know modern control solutions to reliably compensate for voltage fluctuations and ensure sustainable grid quality.

Read more

Training Video

»REGSys®« Training Video 8: Overview SCL-Config for IEC 61850

In this video you will learn how you can export a CID file, how to adjust the IED name and working with the SCL-Config.

Read more

Training Video

»REGSys®« Training Video 7: How to Use the Winconfig Software

In this video you will learn how to create a new parameter file, how to upload setting files or download setting files from the Scada card and what kind of parameters a setting file contains.

Read more

Training Video

»REGSys®« Training Video 6: Firmware Update via Winconfig

In this video you will learn when it is reasonable to use the WinConfig for a firmware update and how to do a firmware update with the WinConfig.

Read more

Training Video

»REGSys®« Training Video 5: Firmware Update via RPL2

In this video you will learn how to create a physical connection before the firmware update, how to use the RPL2 software and how to do a small test after the firmware update.

Read more

Training Video

»REGSys®« Training Video 4: Changing the Default Password

In this video you will learn how to connect the SCADA card to your computer, start the software WinConfig and change the default password and define a new one.

Read more

Training Video

»REGSys®« Training Video 3: Changing IP Address via Winconfig

In this video you will learn how to define a new IP address, how to interpret the “States of detected boards” and how to determine the port numbers of the physical ports.

Read more

Training Video

»REGSys®« Training Video 2: Changing IP-Address via Webserver

In this video you will learn how to access the web server, how to change the network settings in the web server.

Read more

Training Video

»REGSys®« Training Video 1: Adjusting the Time Synchronisation

In this video you will learn how to connect the SCADA card to your computer, start the software WinConfig and change the default password and define a new one.

Read more

General Knowledge

Measuring the Voltage Drop

The voltage drop is the difference between the voltage at the beginning and end of an electrical line. In an electrical network, the voltage can be reduced by the resistance and impedance of the lines, resulting in a lower voltage reaching the consumer than was originally fed in. Find out everything about measurement and calculation in this article!

Read more

Blogpost

International Partner Week 2024 - a Look Back

Our International Partner Week 2024 - many old friends and new faces were our guests, it was a pleasure.

Read more

Contact request:



* Mandatory

Your data is being processed

a-eberle kontakt newsletter ×

The download started automatically in a new window.

How did you hear about us?
Consent to data transfer*

* Mandatory fields