Growing numbers of photovoltaic (PV) systems, electric vehicle (EV) chargers, battery energy storage systems (BESS), heat pumps, and changing industrial loads make low-voltage (LV) networks increasingly dynamic, while many secondary substations and industrial LV distribution systems still lack feeder-level visibility. The A. Eberle LV feeder monitoring solution provides reliable measurement data to assess loading, available capacity, power flows, and load distribution across utility and industrial power networks.
Typical applications:
- Feeder measurement in secondary substations and industrial LV distribution systems
- New secondary substations: »PQI-LV« as the head device, with feeder data integrated via NH strip-type fuse-switch-disconnectors from established manufacturers, e.g. Jean Müller
- Retrofit and industrial LV distribution: »P-Sense« + »V-Sense« + an A. Eberle power quality (PQ) measurement device
- Production lines, peak load and capacity monitoring, data centers, PV, BESS, EV charging and uninterruptible power supply (UPS) systems
- Provision of measurement data for monitoring, analysis, and further processing
This solution is suitable, if:
- A consistent feeder measurement solution is required for utility or industrial LV networks
- Individual feeders need to be systematically measured and evaluated
- Peak load contributors, available electrical capacity or potential overloads need to be identified
- Existing switchgear needs to be digitalized and monitored without being replaced
- Measurement data needs to be stored locally and reliably transferred to higher-level systems
LV Feeder Monitoring for Utility and Industrial Applications
Flexible Measurement Concepts for New Installations, Retrofit and Industry
The A. Eberle LV feeder monitoring solution supports different feeder monitoring concepts depending on the installation. In new secondary substations, »PQI-LV« integrates feeder data via Modbus RTU from NH strip-type fuse-switch-disconnectors. For retrofit projects and industrial LV distribution, »P-Sense« and »V-Sense« are combined with an A. Eberle PQ measurement device. The result is a scalable solution for feeder transparency, local data storage, and data transfer via open interfaces.
Further questions or want to start an enquiry? Please click “Product Enquiry”.
A. Eberle GmbH & Co. KG
Measure. Regulate. Across All Grids.
A. Eberle GmbH & Co. KG, founded in 1980 and headquartered in Nuremberg, Germany, operates in the field of measurement and regulation technology for the energy sector as well as for medium-sized and large industrial companies. Our products and services ensure and enhance the availability of energy supply across all voltage levels and support the integration of renewable energy sources into power grids.


Cross-Product Downloads

Cross-Product Downloads
Special Publications
Flyer
Product Overview A. Eberle
A. Eberle Seminars in Nuremberg

PQI-LV

PQI-LV
Instruction Manual
Installation Manual
Technical Data Sheets
Release Notes
Firmware
Interface Lists
Accessories
Certificates

V-Sense / P-Sense

V-Sense / P-Sense
V-Sense - Technical Data Sheets
P-Sense - Technical Data Sheets
V-Sense/P-Sense - Instruction Manual
Integration Guide for Section 14a EnWG
Tender Template for PQSys as a Solution for Section 14a EnWG
Safety Instructions

WebPQ®
(for fixed installed measuring devices: PQI-DE, PQI-DA smart, PQI-LV)

WebPQ®
(for fixed installed measuring devices: PQI-DE, PQI-DA smart, PQI-LV)
Flyer
Instruction Manual
PostgreSQL - Updates (Patches)
PostgreSQL - Migration
System Requirements
Software Licensing - General Provisions
Security Advisories

Accessories

Accessories
I-Sense: Current Feeder Measurement
Technical Data Sheets
Instruction Manual
I-Sense Flyer
Mounting Panel
Rogowski Coil
Current Clamp
Divisible Differential Current Transformer
GPS Receiver Set
The Complete Solution for LV Feeder Monitoring in Utility and Industrial Power Networks
Reliable Data for Transformer and LV Feeder Loading and Capacity Assessment
Reliable measurement data is essential for assessing the actual loading of transformers and individual LV feeders, identifying available capacity and supporting operational decisions. The solution provides a consistent data basis for monitoring, analysis and planning across utility and industrial power networks.


»PQI-LV« - The Central Device for LV Feeder Monitoring
»PQI-LV« serves as the central device for acquiring, processing, storing, and providing measurement data in the secondary substation. It combines its own voltage and current measurements with feeder data integrated via Modbus RTU. Depending on the installation, feeder data is provided by NH strip-type fuse-switch-disconnectors or by »V-Sense« and »P-Sense«. Measurement data can be stored locally and transferred to higher-level systems via various supported communication protocols.
»V-Sense« - Central Voltage Sensor
In secondary substations and industrial LV distribution systems, »V-Sense« provides the central voltage measurement for the connected »P-Sense« devices. It supplies the P-Sense bus with 24 V DC and simultaneously transfers the measured voltage values via galvanically isolated outputs.
»P-Sense« - Current and Power Measurement per LV Feeder
»P-Sense« measures the currents of individual outgoing LV feeders using Rogowski coils. It continuously measures AC currents from 1 A to 1,600 A with a frequency bandwidth of up to 3 kHz. In combination with »V-Sense«, active power, reactive power, and cos φ are available per feeder, providing valuable data for load, capacity and energy monitoring.
Open Data Interfaces for Integration into Existing Systems
The A. Eberle LV feeder monitoring solution enables flexible provision of measurement data centrally via the WebPQ® platform using a REST API or decentrally directly via the measurement devices as RTUs. In the decentralized approach, the devices provide data via MQTT or IEC 60870-5-104, enabling integration into SCADA systems, energy management systems, and applications for grid state assessment or grid calculation.
The modular architecture simplifies integration into secondary substations, industrial LV distribution systems, and existing switchgear configurations.
LV Feeder Monitoring in New and Existing Installations
Flexible LV Feeder Measurement
NH Fuse-Switches (New Substations) vs. »V/P-Sense« (Retrofit & Industry)
Different measurement concepts are available depending on the installation and application.
New Secondary Substations
In new secondary substations, »PQI-LV« is integrated via Modbus RTU with NH strip-type fuse-switch-disconnectors from established manufacturers, such as Jean Müller. Additional sensors and third-party components can also be integrated via Modbus RTU.

Retrofit & Industrial LV Distribution
For retrofit projects and industrial LV distribution, »P-Sense« is combined with »V-Sense« and an A. Eberle PQ measurement device. Using Rogowski coils, the concept enables flexible feeder monitoring and digitalization of existing switchgear without replacing the installation.

Real World Example: Full LV Feeder Visibility in an Existing Secondary Substation
Retrofit, Don't Replace - Feeder-Level Transparency Made Simple


More visibility without touching the existing switchgear: in this secondary substation, feeder monitoring was retrofitted with »PQI-LV«, »V-Sense« and »P-Sense«. »P-Sense« captures the current of every individual LV feeder via Rogowski coils, »V-Sense« delivers the central voltage measurement, and »PQI-LV« brings it all together - collecting, storing and processing the data as the foundation for further analysis.
The transformer main infeed benefits too: it's measured to power quality Class A (IEC 61000-4-30), with optional disturbance recording available as a retrofit. Current sensing at the transformer is flexible - Rogowski coils, or standard mV signals where conventional current transformers (CTs) are already in place. And since »PQI-LV« doubles as an MQTT gateway, there's no need for extra gateway hardware - a real cost advantage.
The result: a reliable, structured data foundation for every feeder and the true grid situation - with zero disruption to the existing switchgear. The same concept works just as well in industrial LV main and sub-distribution systems.
- Application: Retrofit of an existing secondary substation - no switchgear replacement
- Measurement: Current and power per LV feeder, plus transformer main measurement in PQ Class A with optional disturbance recording
- Flexibility: Current sensing via Rogowski coils or mV signals from conventional CTs
- Cost advantage: »PQI-LV« as an integrated MQTT gateway - no extra hardware required
- Customer benefit: Full feeder-level transparency as the basis for load and capacity assessment, and further data processing
- Also applicable to: Industrial LV main and sub-distribution systems
IT Security by Design for Utility and Industrial LV Systems
The measurement solution with »PQI-LV« as the central device provides IT security features including audit logging, encryption technologies, and User Rights Management (URM) with Role Based Access Control (RBAC).

WebPQ® - Central Platform for LV Feeder Monitoring
Analysis, Visualization, and Secure Provision of Measurement Data in One Platform

WebPQ®
Central Analysis of LV Measurement Data
WebPQ® is the central analysis platform for evaluating and providing measurement data from secondary substations and industrial LV distribution systems. It enables structured analysis, visualization, alarming, reporting, and further processing of measurement data across individual installations and larger device fleets. WebPQ® is available for on-premises operation and as a SaaS solution.
Do You Have Any Further Questions About
LV Feeder Monitoring?
Our Specialists Will Be Happy to Help You!