What Is Power Quality?
Power Quality describes how closely the voltage actually supplied to a consumer corresponds to the voltage promised by the utility company. Various factors influence voltage quality:
- Power generators and the structure of the utility company’s distribution network
- Transmission of the mains voltage
- Influences caused by consumers and connected equipment
Supply reliability depends on the extent to which an electrical distribution network fulfils its supply tasks within a defined period. Modern measurement technology, such as our portable power quality analysers and fixed-installed power quality analysers, makes an important contribution to maintaining voltage quality in low-voltage networks.
Without suitable measuring equipment, neither the quality of individual voltage characteristics nor the causes of disturbances can be assessed reliably.
The required electrical supply quality at the point of connection is regulated by various standards for generation, consumption and distribution grids, including DIN EN 50160, VDE-AR-N 4120 and IEC 61400-21. These requirements also form part of the basis for grid connection agreements.
Power quality measuring devices are required to determine harmonic levels and the THD factor, meaning Total Harmonic Distortion. They calculate relevant electrical power quality parameters from measured voltage and current signals and support systematic fault analysis. They can also identify harmonics that may interfere with electronic components and significantly shorten their service life.
Power Quality at a Glance
- Power quality assessment considers characteristics such as frequency, voltage, harmonics, flicker and voltage unbalance.
- Power quality measuring devices record voltage and current signals, calculate relevant parameters and support fault analysis.
- Different standards apply depending on the network, voltage level and application.
Power Quality Evaluation Criteria
Causes and Consequences of Poor Voltage Quality
The following overview summarises the characteristics discussed in this article. Detailed definitions, causes and consequences are provided in the accordion below.
| Quality characteristic | What is evaluated? |
|---|---|
| Frequency deviation | Deviations in grid frequency based on 10-second average values |
| Voltage dips and swells | Temporary voltage levels below or above specified thresholds |
| Harmonics and THD | Distortion of the sinusoidal waveform caused by harmonic components |
| Rapid voltage changes | Transitions from one steady-state voltage condition to another |
| Flicker | Periodic voltage fluctuations and the resulting flicker values |
| Voltage unbalance | Uneven loading within a three-phase system |
| Supply interruption | Voltage on all phases falling below 5% of the nominal value |
Frequency Deviation
Frequency deviation events are evaluated using 10-second average values of the grid frequency.
The permitted deviation limits distinguish between synchronous networks (±1% = 0.5 Hz) and islanded networks (±2% = 1 Hz).
Large frequency deviations can be caused by sudden disconnections of major loads or generation plants. Excessive deviations may cause motors and generators to lose synchronism and can consequently damage them.

Voltage Dip
A voltage dip is a temporary decrease in the RMS voltage below a specified dip threshold at a particular point in the electricity supply network. It can be caused by the connection of loads.



Explanation of terms:
Extreme value: Lowest value of the 10 ms voltage during the event [V]
Duration: Time between leaving and returning to the nominal voltage range [ms]
Voltage Swell
A voltage swell is a temporary increase in the RMS voltage above a specified initial threshold at a particular point in the electricity supply network. It can be caused by the disconnection of loads.



Explanation of terms:
Extreme value: Highest value of the 10 ms voltage during the event [V]
Duration: Time between leaving and returning to the nominal voltage range [ms]
Total Harmonic Distortion (THD) and Harmonics
THD is the ratio of the combined RMS values of all harmonics to the RMS value of the fundamental component. It indicates the total distortion caused by non-linear loads.
Causes:
Non-linear loads in the supply network can distort the sinusoidal voltage waveform. Depending on the type of load, particular multiples of the grid frequency may become especially pronounced.
For three-phase loads such as synchronous or asynchronous motors and B6 rectifiers, the 5th, 7th, 11th and 13th harmonics can be particularly significant. For single-phase low-voltage loads, multiples of three are often affected, including the 15th, 21st and 27th harmonics.
A harmonic distortion is recorded as a PQ event when the 10-minute average value exceeds the limit defined by the applicable standard. The event indicates the harmonic order and the percentage by which the limit has been exceeded.
Excessive voltage harmonics can result in malfunction, overheating, equipment failure and increased audible noise.



Rapid Voltage Change (RVC)
Rapid voltage changes occur relatively frequently in electricity supply networks and are mainly caused by changes in customer loads and switching operations within the grid.
An RVC event is characterised by the grid voltage changing from one steady state to another. The event records the duration of this transition, the maximum voltage deviation during the transition and the resulting steady-state voltage change.
Rapid voltage changes usually have no major effect on electrical equipment. However, frequent RVC events may increase the flicker level.



Flicker
Flicker is a measure of periodic voltage fluctuations in an electrical network that can cause visually perceptible changes in the brightness of electrical lamps.
Using the flicker measurement method according to DIN EN 61000-4-15, these fluctuations are calculated as dimensionless values and averaged over two time intervals using a weighted method. Short-term flicker Pst is calculated over a 10-minute interval, while long-term flicker Plt is calculated over a 2-hour measurement interval.
Causes:
Increased flicker values are commonly caused by periodic power fluctuations in networks with high impedance. High harmonic currents and interference between loads may also cause flicker limits to be exceeded.
Power quality events such as temporary overvoltages or undervoltages can also cause the flicker limit of the affected voltages to be exceeded.
Significance for EN 50160 evaluation:
EN 50160 does not define limits for the number of Pst and Plt events. Only the weekly statistics of long-term flicker Plt in the 2-hour interval are evaluated.



Voltage Unbalance
Voltage unbalance is a measure of uneven loading within a three-phase system. It may be indicated by different phase amplitudes ΔU or by a phase-angle difference Δϕ that is not equal to 120° between the phase-to-phase voltages.
The 10-minute average values of the symmetrical components of the measured voltage system are used to calculate voltage unbalance. The percentage value is calculated from the ratio of the negative-sequence component to the positive-sequence component.
Causes:
Three-phase system unbalance occurs mainly in low-voltage networks and can be caused by unevenly distributed single-phase and two-phase loads or generation plants. In medium- and high-voltage networks, unbalance may be caused by melting furnaces or transposed transmission lines.
Significance for EN 50160 evaluation:
EN 50160 does not specify limits for the number of voltage-unbalance events. Only the weekly statistics of the 10-minute voltage-unbalance measurement values are evaluated. The limit is usually 2%.



Power Supply Interruption
A power supply interruption is characterised by the voltage on all phases falling below 5% of the nominal value.
A distinction is made between scheduled and unscheduled interruptions within a particular area, short interruptions lasting up to 3 minutes and long interruptions lasting more than 3 minutes.
Interruptions may be caused by external influences such as damage to transmission lines during natural events, planned switching operations or the operation of protection devices.



Our Video Series
Current Topics Relating to Voltage Quality
The videos in this section are available in German only.
Changes in Energy Technology - Part 1
This article, produced together with the web portal Schutztechnik.com, discusses current changes in energy technology. It also considers the effects of grid disturbances and their influence on measuring devices used to detect faults in the network.
Changes in Energy Technology - Part 2
Standards play an important role in voltage-quality measurements. They must therefore be adapted to changing conditions in energy technology. The second article in the series examines current standards and their interpretation with regard to high switching frequencies.
Power Quality Measurements:
The Neutral Conductor and Harmonics
Power quality measurements frequently reveal limit violations involving odd harmonics such as the 15th, 21st and 27th orders. This article explains what harmonics are, how they arise and how they affect the neutral conductor.
Power Quality Measurements:
The 3rd Harmonic in Practice
The report “The Neutral Conductor and Harmonics” explains the special characteristics of harmonics divisible by three and why they add together in the neutral conductor. This publication illustrates the issue using a typical network measurement and explains which aspects should be considered when performing power quality measurements. The case concerns voltage-quality problems in an office building.
Our Portable Power Quality Analysers for Acute Fault Detection in the Grid
The PQ-Box family consists of powerful portable network and frequency analysers, power measuring devices and transient recorders. User-friendliness and practical operation were central considerations during their development.
More Information
Special Publications
Application Examples for Our Measuring Devices
Our Fixed-Installed Power Quality Devices for Continuous Grid Monitoring
Fixed-installed fault recorders and network power quality analysers are central components of systems that handle measurement tasks in low-, medium- and high-voltage networks.
More Information
Important Power Quality Standards
An Overview
The following overview summarises commonly used international standards relating to electrical supply quality. When evaluating a particular measurement point, the standards applicable to the specific network must be considered. Some standards apply only to particular voltage levels. In most cases, low voltage is defined as below 1 kV, medium voltage as 1 to 35 kV and high voltage as above 35 kV.
EN 50160
Description:
Voltage characteristics in public electricity supply networks.
Parameters considered:
- Frequency
- Voltage
- Flicker
- Voltage harmonics
Applicable to:
Low-, medium- and high-voltage networks in public European grids
IEC 61000-2-2
Description:
Compatibility levels for low-frequency conducted disturbances and signalling in public low-voltage power supply systems.
Parameters considered:
- Frequency
- Voltage
- Flicker
- Voltage harmonics and frequency bands up to 150 kHz
Applicable to:
Public low-voltage networks
IEC 61000-2-12
Description:
Compatibility levels for low-frequency conducted disturbances and signalling in public medium-voltage power supply systems.
Parameters considered:
- Frequency
- Voltage
- Flicker
- Voltage harmonics
Applicable to:
Public medium-voltage networks
IEC 61000-2-4
Description:
Compatibility levels for low-frequency conducted disturbances in industrial plants.
Parameters considered:
- Frequency
- Voltage
- Flicker
- Voltage harmonics
Applicable to:
Industrial low-voltage networks
IEEE 519
Description:
Recommended practice and requirements for harmonic control in electric power systems.
Parameters considered:
- Voltage harmonics
- Current harmonics
Applicable to:
Industrial low-, medium- and high-voltage networks
IEC 61000-3-12
Description:
Limits for harmonic currents produced by equipment with an input current above 16 A and up to 75 A per phase intended for connection to public low-voltage systems.
Parameters considered:
- Current harmonics
Applicable to:
Public low-voltage networks
Power Quality Services
We provide power quality audits and fault investigations in accordance with EN 50160 and the IEC 61000 series. Our specialists support you with expertise, suitable network analysers and the required measurement accessories. Based on the recorded data and evaluation, we work with you to develop an appropriate solution.
More Information
FAQ About Power Quality
What does Power Quality mean?
Power Quality describes how closely the voltage supplied to a consumer corresponds to the voltage promised by the utility company.
Which characteristics are evaluated in a power quality assessment?
The characteristics covered in this article include frequency deviation, voltage dips, voltage swells, harmonics and THD, rapid voltage changes, flicker, voltage unbalance and supply interruptions.
Why are power quality measuring devices required?
They record voltage and current signals, calculate electrical supply quality parameters and help identify disturbances and their possible causes.
What is the THD factor?
THD describes the ratio of the combined RMS values of all harmonics to the RMS value of the fundamental component. It indicates the total distortion caused by non-linear loads.
Which standards are relevant to Power Quality?
The article covers EN 50160, IEC 61000-2-2, IEC 61000-2-12, IEC 61000-2-4, IEEE 519 and IEC 61000-3-12. The applicable standard depends on the network, voltage level and application.
When are portable and fixed-installed power quality analysers used?
Portable analysers are primarily used for temporary measurements and acute fault investigation. Fixed-installed devices are used for continuous monitoring of electrical networks.












