Hot-Spot Temperature and Service Life of Transformers

Info Letter No. 16

Power transformers are key components of an electrical supply grid.

The failure of a transformer not only has major economic consequences for the energy supplier, it can also lead to serious losses for consumers. For this reason, it makes sense to monitor the transformer as closely as possible, to take its “temperature curve” (the thermal image) so as to collect information about the current load and the expected remaining life. This task can – based on IEC standards – be solved by electronic measurement and computing facilities.

The thermal situation in the transformer can be represented graphically (see Figure 1), where this is a simplified view of a complex situation.

The Following Simplifications Are Necessary:

  1. it is assumed that the oil temperature in the tank increases linearly from the bottom to the top.
  2. Another assumption is that the average temperature of the winding is also linearly parallel to the oil temperature with a constant temperature differential gr increasing from the bottom to the top.
  3. it is assumed that the hot spot temperature (P) is higher than the temperature of the winding (hot) at the upper end of the winding. The increase in temperature between the hot spot in the winding and the oil temperature in the tank is designated as a constant Hgr  (hot spot at top oil gradient). Studies have been able to prove that the factor H, depending on the transformer size, short-circuit impedance and winding design, can vary between 1.0 and 2.1.

To determine the hot-spot temperature, in addition to the oil temperature Q0 a phase current I and some transformer-specific characteristics are required.

In most cases, this interpretation will lead to sufficiently good results, because it may be assumed that the transformer is loaded approximately uniformly.

In this case: I1 ~ I2 ~ I3

Automatic Voltage Regulation With REGSys® – Proven a Thousand Times Over, Multifunctional and Flexible

Need More Information?

Contact Us!


Contact

News From the Product Group

REGSys® - News

Blogpost

International Partner Week 2024 – a Look Back

Our International Partner Week 2024 - many old friends and new faces were our guests, it was a pleasure.

Read more

General Knowledge

REGSys® Parallel Regulation of Transformers With Tap-Changers

The regulation of transformers with tap changers is an essential subject within the field of power supply and distribution. Today these tasks are accomplished electronically with high regulation quality. Digital regulators, such as the freely programmable REGSys® voltage regulator system, are in use.

Read more

Info letter

Info Letter No. 13: Parallel Operation of Step Transformers

The rule of thumb that with parallel operation of transformers the ratio of the rated outputs should not...

Read more

Info letter

Info Letter No. 11: Voltage Regulation With Step Transformers in Parallel to Busbars (Part 3)

Direct measurement of the circulating current is not possible with the usual measurement...

Read more

Info letter

Info Letter No. 10: Voltage Regulation With Step Transformers Parallel to Busbars (Part 2)

The following considerations apply to a symmetrical operation of a three-phase network, so that the...

Read more

Info letter

Info Letter No. 9: Voltage Regulation With Step Transformers in Parallel to Busbars (Part 1)

Within a station, the transformers are in close proximity. Therefore, the line impedances between the...

Read more

Info letter

Info Letter No. 7: Load-Dependent Voltage Change

For the regulation of the voltage ULoad at a predetermined value at the specified load point (e.g. the...

Read more

Info letter

Info Letter No. 4: Summation of Alternating Currents

For the parallel connection of power sources, the principle of superposition applies, when all resources...

Read more

Special Publication

Regulating the Active and Reactive Power With REGSys®

he voltage regulator REG-D(A) is normally tasked with controlling voltage on the secondary side of a transformer. The main task here is to achieve the best possible balance between voltage stability and the number of taps...

Read more

Special Publication

The REGSys® Triple-Wound Feature

Since then, it has become possible to use the feature for other application such as so-called “energetic recovery” or to implement applications requiring a second voltage (U1, U2) and current (I1, I2) measurement. In these...

Read more

Special Publication

Safely Regulate the Load Flow

Phase-shifting transformers or shunt regulators are special power transformers. They allow the active power flow (load flow) in alternating current networks to be controlled. During tapping, the ...

Read more

Contact request:



* Mandatory

Your data is being processed

a-eberle kontakt newsletter ×

Our seminars &
webinars

► Register here!

x