Transient Relay for High Resistance, Intermittent and Recurrent Earth Faults (Part 2)

Info Letter No. 18

Static Earth Fault

Figure 3 can also be used for the determination of static earth faults.  In an isolated network the entire capacitive current of all outputs flows through the point of failure. The relays in the healthy outlets measure a capacitive zero current and the relay in the faulty output measures an inductive zero current. With a stationary earth fault, the value of the inductive zero current is the same as in the previous section, the value of the zero current of the healthy outputs at the back of the relay.

In compensated networks, the situation changes. In this case, the current overlaps through the Petersen coil and reduces the capacitive current through the point of failure. In an ideal matching network, the capacitive current through the failure point is fully compensated. From Figure 3, it is evident that, in this case, the relay in the faulty output also measures a capacitive zero current as well as the relays in the healthy outputs. Therefore, in a compensated network the inductive nature of the zero current is no longer an indication of a faulty output.

Through the use of Petersen coil, the current can be reduced to on a small active current, which is usually in the range of 2 % to 3 % of the total capacitive phase-earth current.

Overlay

At the first ignition of the arc, the superposition of three operations begins.

The following figures show two different earth faults for a compensated 20 kV network with three outputs and a capacitive current of 108 A and 5 A overcompensation. The network corresponds to the configuration in Figure 3. The low resistance earth fault has a value of 10 ohms, and the high-resistance earth faults have a value of 2000 Ohms. The recording was made with a sampling rate of 10 kHz.

The high frequency discharge oscillation is greater in the case of a low-resistance earth fault.

In the case of the high resistance fault, the zero voltage in the steady state reaches only 40%.

Conventional Transient Relay

The conventional transient relay evaluates the charging process for the directional decision concerning the earth fault. If the zero sequence voltage u0 exceeds a set threshold offset, a narrow window is used for measuring the zero current i0. The direction decision is made by comparing the sign of i0 with the sign of u0 during this test window.

The earth fault is in the direction of the output when the sign of i0 does not correspond to the sign of u0. If the signs are the same, the fault is in the direction of the busbar.

When the ignition is at the time u1E = 0 V, there is no discharge oscillation.

The charging oscillation is present in all cases and can be evaluated by the transient relay.

Need More Information?

Contact Us!


Contact

Info-Letters

Click Through Our Info Letter Series

News From the Product Group

EORSys - News

Webinar

»EORSys« Webinar: Digital Secondary Substations in the Distribution Grid of the Future

Webinar recording from 2024-05-07: »PQMobil - Digital Secondary Substations in the Distribution Grid of the Future«.

Read more

Blogpost

International Partner Week 2024 – a Look Back

Our International Partner Week 2024 - many old friends and new faces were our guests, it was a pleasure.

Read more

Webinar

»EORSys« Webinar: Future-Proof Integration of Digital Substations in the Distribution Grid

Webinar recording from 2024-07-11: »EORSys - Future-proof Integration of Digital Substations in the Distribution Grid«.

Read more

Webinar

»EORSys« Webinar: Short-Circuit & Earth Fault Detection in Digital & Analog Substations

Webinar recording from 2024-05-07: »EORSys - Short-Circuit & Earth Fault Detection in Digital & Analog Substations«.

Read more

General Knowledge

The Future of the Distribution Grid: Focus on Digital Secondary Substations

In this technical report, Gerald Jacob (Product Manager »EORSys«) uses a specific example to illustrate how distribution system operators can meet the challenges of energy transition in the medium and low-voltage grid with future-proof secondary substations.

Read more

General Knowledge

Earth fault explained – basics and functions of an electrical phenomenon

Everything you need to know about earth faults - from the basics, causes and examples to the consequences. Find out more in this article about earth fault clearing, compensation, location and the benefits of constant monitoring to ensure a safe power grid.

Read more

General Knowledge

Ready for the Smart Grid of the Future?

All information about smart grids/intelligent power grids, the technology behind them, advantages, disadvantages, challenges and current distribution.

Read more

Special Publication

Cost Efficient Management of Digital Secondary Substations: Earth Fault Indicator EOR-3DS as Digitisation Unit for Secondary Substations

Digital secondary substations are becoming a key element for distribution system operators in terms of automation, monitoring, and efficient operations of their networks. Read this technical report about the EOR-3DS in its role as digitisation unit for secondary substations.

Read more

Blogpost

Kick-off for Mass Rollout of the Digital Local Network Station at »Netze BW«

Our product manager Gerald Jacob (»EORSys«) with a short Q&A at the official kick-off event of the digital secondary station »FFU 2.0«.

Read more

Blogpost

Brand New: Short-Circuit and Earth Fault Indicator EOR-3DS Released on 27.03.2023

New combined earth fault and short circuit indicator EOR-3DS: AVAILABLE FOR ORDER NOW

Read more

Blogpost

Product Announcement: Short and Earth Fault Locator EOR-1DS Released 05.08.2022

We are pleased to inform you that the product »Combined Earth Fault and Short Circuit Indicator EOR-1DS« is officially released as of today.

Read more

Info letter

Info Letter No. 21: The Influence of the Contact Resistance at the Earth-Fault Location on the Zero Sequence Voltage UEN in Compensated Networks

The earth fault in compensated networks is usually presented without a contact resistance at the fault...

Read more

Info letter

Info Letter No. 20: Capacitance of Conductors

In the conductors of electrical power supplies, a distinction is made between the operating capacitance...

Read more

Info letter

Info Letter No. 17: Transient Relay for High Resistance, Intermittent and Recurrent Earth Faults (Part 1)

The statistics show that earth faults constitute a large proportion of network faults. Conventional relays...

Read more

Info letter

Info Letter No. 15: Earth Fault Location Using the Harmonic Procedure (Part 2)

For the study of the behaviour of the harmonic currents and voltages in the compensated network, at...

Read more

Info letter

Info Letter No. 14: Earth Fault Location Using the Harmonic Procedure (Part 1)

For the following considerations a network with three outputs and an earth fault in line 1 in output...

Read more

Info letter

Info Letter No. 6: Detection of Transient Earth Faults

When there is an earth fault in a conductor, at the start of the earth fault three events occur at the...

Read more

Info letter

Info Letter No. 4: Summation of Alternating Currents

For the parallel connection of power sources, the principle of superposition applies, when all resources...

Read more

Contact request:



* Mandatory

Your data is being processed

a-eberle kontakt newsletter ×

Our seminars &
webinars

► Register here!

x